The WB6830R2-P Three phase electric parameter acquisition module can monitor the voltage, current, reactive power, apparent power, power factor, frequency and other parameters of the power grid, and the operation state of the power grid with wrong phase and phase breaking. It can measure positive and negative electric energy, active and reactive electric energy, four-quadrant reactive electric energy, time electric energy and monthly electric energy; and can analyze the 2~31 times harmonic content of voltage and current, total harmonic content (THD), imbalances of voltage and current & components of positive sequence and negative sequence and zero sequence, the current K coefficient, the voltage wave peak coefficient and so on. The maximum demand for average phase current, active and reactive power and apparent power can be calculated. When using this product, it must communicate through the RS485 interface and according to the specified protocol to get the required digital electrical parameter value.


Product Detail

Product Tags

Product Description And Application

The WB6830R2-P Three phase electric parameter acquisition module can monitor the voltage, current, reactive power, apparent power, power factor, frequency and other parameters of the power grid, and the operation state of the power grid with wrong phase and phase breaking. It can measure positive and negative electric energy, active and reactive electric energy, four-quadrant reactive electric energy, time electric energy and monthly electric energy; and can analyze the 2~31 times harmonic content of voltage and current, total harmonic content (THD), imbalances of voltage and current & components of positive sequence and negative sequence and zero sequence, the current K coefficient, the voltage wave peak coefficient and so on. The maximum demand for average phase current, active and reactive power and apparent power can be calculated. When using this product, it must communicate through the RS485 interface and according to the specified protocol to get the required digital electrical parameter value.

As an advanced intelligent and digital frontend acquisition module of power grid, the product can be applied to various control systems, energy management systems, substation automation, distribution automation, industrial automation, intelligent distribution plate, residential power monitoring, intelligent building, switchgear and so on.

It has the characteristics of convenient installation, simple wiring, convenient maintenance, small engineering quantity and programmability.

Product Dimensional Drawing (unit: mm)

Product Terminals Identification Drawing

Terminals Definition

Terminals name

Mark

Definition

Auxiliary power terminals

+E

Positive electrode of auxiliary power

G

Grounding of auxiliary power

Detection terminal of AC voltage

UaUbUc

ABC Inlet terminals of three-phase voltage

Un

Common zero line

NC

No connection

Detection terminal of AC current

Ia+Ia-

Inlet and outlet terminals of the A phase current

Ib+Ib-

Inlet and outlet terminals of the B phase current

Ic+Ic-

Inlet and outlet terminals of the C phase current

RS485 Interface

A

RS485A

B

RS485B

Output terminals of pulse

P+

Pulse output +

P

Pulse output

Key Technical Data

Attribute

Value

Measurement network

3 phase 4 wire, 3 phase 3 wire, Single phase;

Input

AC 0~500V,

AC 1A~5A (The range can be reached to 10A~400A after increasing the external CTs);

Frequency Range

45Hz~65Hz

Power Consumption

Voltage: ﹤0.5VA (each phase, resistance input)﹥2MΩ,

Current:﹤0.1VA (each phase);

Accuracy

Voltage & Current: 0.2%, Frequency: 0.02Hz,

Active/Reactive/Apparent Power: 0.5%,

Active / Reactive Electric Energy: Class 1 / Class 2,

Harmonic: Grade B (GB/T14549-93), 2~31 times.

Responding Time

≤ 100ms

Communication Mode

Half-duplex,RS485;

Communication Protocol

MODBUS-RTU, DL/T645-1997 (2007) (optional);

Baud Rate

2400/4800/9600/19200BPS, DIP switch (default: 9600BPS);

Pulse Output

Open-collector output of 1 path optocoupler,

Pulse constant: maximum 20000 imp/kWh (kvarh), default 3200;

Overload Capacity

Voltage: 1.2 times, instantaneous overload:2 times / 5s,

Current: 1.2 times, instantaneous overload:10 times / 5s;

Auxiliary Power

DC +12V, +24V (See product label);

EMC index of power supply and output ports

ESD: terminal contact discharge: 6kV,

Surge: voltage port: 6kV, Power supply and communication port: 4kV,

Electric fast transient pulse group: 2kV/5kHz,

Conduction anti-interference: 3V, 150kHz~80MHz,

Radiation anti-interference: 10V/m, Analog interference: 80MHz~ 1GHz,

Digital interference: 800MHz ~ 9600MHz, 1.4GHz~2.0GHz;

Isolation Voltage

DC 2.5kV, 1minute (Among input, output, auxiliary power and shell);

Static Current

≤ 100mA

Ambient Temperature

-25℃~+70℃

Humidity

≤ 93% RH (without corrosion and condensation)

Altitude

≤2500m

Weight

250g