2fcbee89

Dc Current Sensor With Analog Output WBI344U01-S

Dc Current Sensor With Analog Output WBI344U01-S

WBI344U01-S adopts the principle of modulation and demodulation isolation to measure the DC current in the power grid or circuit in real time, and convert it into a standard DC current output; it has the characteristics of high precision, high isolation, low drift, and wide temperature range. Input and output circuits are completely isolated, and all output signals share the same ground with the power supply, which can be directly connected with various types of A/D converters to form a centralized data acquisition system. This product is suitable for real-time detection of power systems, post and telecommunications systems, railway monitoring systems, etc.


Product Detail

Product Tags

Product Description and Application

WBI344U01-S adopts the principle of modulation and demodulation isolation to measure the DC current in the power grid or circuit in real time, and convert it into a standard DC current output; it has the characteristics of high precision, high isolation, low drift, and wide temperature range. Input and output circuits are completely isolated, and all output signals share the same ground with the power supply, which can be directly connected with various types of A/D converters to form a centralized data acquisition system. This product is suitable for real-time detection of power systems, post and telecommunications systems, railway monitoring systems, etc.

Product Dimensional Drawing (unit: mm)

Product Terminal Identification Drawing

Key Technical Data

Attribute

Value

Input

DC 0-1mA...…0-5A

Output

DC(0)4-20mA

Accuracy

0.2%

Input impedance (R)

Ri=0.05V/Ix (Ix is the current be measured)

Linear range

5.0-120% of nominal input

Responding time

150ms

Over load capacity

10 times of nominal input, for 5 seconds

Maximum load

6-12V

Static current

17mA

Auxiliary power

+12Vdc +24Vdc

Isolation voltage

≥2500Vdc, for 1 minute

Output ripple

<10mA

Drifting by temperature

200×10-6/℃

Ambient temperature

-10℃~+50℃

Mounting

DIN rail 35mm mount

Standard application

1. Accuracy

1.1 Accurate degree is conformed to IEC688:1992

2. Safety

2.1 Overload capability

Overload capability is conformed to IEC688:1992

2.2 Isolation voltage

Can be endured testing voltage is conformed to Q/72085584-0.1-2004

2.3 Insulation impedance

The insulation impedance is no less than 20M Ohm, is conformed to Q/72085584-0.1-2004

3. Electromagnetic Capability

3.1 Electromagnetic field immunity test according to IEC 61000-4-3:1995

3.2 Power frequency magnetic field immunity test according to IEC 61000-4-8:1993


  • Previous: