Ce Certification Electrical Isolation Transducer WBV412H29

Ce Certification Electrical Isolation Transducer WBV412H29

WBV412H29 converts AC input voltage into a load independent output signal DC 0V-5V or 1V-5V. It has adopted electromagnetic isolation principle and average measurement method for real time measurement of AC voltage from electric net or electric circuit.

The product has certain advantages of total galvanic isolation among input、output and auxiliary power, high accuracy, low drifting by temperature, and wide temperature bearable range, etc. The product meets EN61326:2006 and EN60100:2001 standard.


Product Detail

Product Tags

WBV412H29 AC Voltage Transducer

Product Description and Application

WBV412H29 converts AC input voltage into a load independent output signal DC 0V-5V or 1V-5V. It has adopted electromagnetic isolation principle and average measurement method for real time measurement of AC voltage from electric net or electric circuit.

The product has certain advantages of total galvanic isolation among input、output and auxiliary power, high accuracy, low drifting by temperature, and wide temperature bearable range, etc. The product meets EN61326:2006 and EN60100:2001 standard.

Product Dimensional Drawing (unit: mm)

Terminal definition table

1 IN
3 IN
6 L
7 N
9 OUT-
10     OUT+

Key Technical Data

Attribute

Value

Input

AC 10V-1000V

Output

DC 0-5V or 0-10V

Accuracy

0.2%

Input impedance (R)

Ux≥10V Ri=Ux×1kΩ/V

Linear range

0-120% of nominal input

Responding time

200ms

Over load capacity

2 times of nominal input, for 1 second , repeat 10 times with 10 seconds’ interval

Maximum load

7.5mA

Auxiliary power

AC/DC 85V-265V

Isolation voltage

input and output≥2500Vdc, for 1 minute

Auxiliary Power and input≥2500Vdc, for 1 minute

Auxiliary Power and output≥2500Vdc, for 1 minute

Output ripple

≤10mV

Drifting by temperature

350×10-6/℃

Ambient temperature

-25℃~+70℃

Product Input-Output characteristic curve

Instruction of Installation

  1. 1. The product has adopted structure compliance with EN50022; suitable for DIN rail mounting NS35/7.5, NS35/15. Installation steps are as following (please reference to dimensional drawing):

    Step 1: Immobilize one side of product‘s mounting trough to the DIN mounting rail;

    Step 2: Pull out the spring clasp;

    Step 3: Place whole mounting trough to the DIN mounting rail properly;

    Step 4: Release spring clasp to make sure the installation.

    2. The product has calibrated before out of factory. After correctly wiring, it can be powered and used immediately. But for further precise signal sampling, user need to warm-up the product for 3 minutes before use.

    3. Basic testing method for accuracy

    (1) According to the terminal definition table to connect the testing circuit;

(2) The testing must to be done by under the following conditions

Auxiliary power: nominal input±5

Ambient temperature: 25℃±5

Relative humidity: RH(4575)

Accuracy for Signal Power Source instrument: 0.05

(3) warming up the transducer for 3 minutes

(4) using output monitoring meter V1 to measuring the output of signal power source instrument, set a any input value which is within the measuring range of the transducer Ur. (for e.g. if input value is 100V, the output is 0V-5V, the expected output value Uz should be calculated as:

Uz=5V×Ur/100V

(5) using output monitoring meter V2 to measuring the output voltage V0 of the transducer, the basic introduced errorγof the transducer should be calculated as:

γ= (UoUz)/5V×100%

(6) Repeating (4) (5), if calculated absolute value is less than the given accuracy value of the transducer, it shows the transducer’s accurate grade is qualified.