WBI412N95 uses a special isolation module to measure the AC current in the grid and circuit in real time and transform it into the standard DC voltage output; it has the advantages of high precision, high isolation, wide frequency response, low drift, low power consumption, wide temperature range, strong anti-interference ability, wide operating power range and so on. This product adopts card-mounted structure, terminal wiring, easy installation, input, output, power supply three isolation, suitable for power equipment, power network monitoring automation system, industrial control monitoring system, railway signal system.


Product Detail

Product Tags

Product Description And Application

WBI412N95 uses a special isolation module to measure the AC current in the grid and circuit in real time and transform it into the DC voltage (Uz) output of the standard vertebra; with high precision, high isolation, wide frequency response, low drift, low power consumption, wide temperature range, strong anti-interference ability, wide operating power range and so on. This product adopts card-mounted structure, terminal wiring, easy installation, input, output, power supply three isolation, suitable for power equipment, power network monitoring automation system, industrial control monitoring system, railway signal system.

Product Dimensional Drawing (unit: mm)

Terminals Definition

Key Technical Data

Attribute

Value

Input

0.5A, 1A, 5A-50A AC

Output

0-5V, 0-10V DC

Accuracy

0.2%

Frequency range

25Hz~5kHz

Input impedance (R)

Measuring current<100mA, input impedance 200Ω

Measuring current ≥100mA, input impedance approximate zero

Linear range

0-120% of nominal input

Responding time

300ms

Over load capacity

30 times of nominal input, for 5 seconds

Output impedance (Output current)

6V

Auxiliary power

+9V-+36V DC

Isolation voltage(Input/Output)

2500Vdc, for 1 minute

Output ripple

<10mV

Drifting by temperature

1.5x10-4/℃

Ambient temperature

-25℃~+70℃

Mounting

DIN rail 35mm mount or screw mount

Surge immunity (see IEC61000-4-5)

ontact discharge 6KV, air discharge 8KV, performance criterion A

Electrostatic discharge immunity (see IEC61000-4-2)

contact discharge 6KV, air discharge 8KV, performance criterion A

Radio frequency electromagnetic field radiation immunity (see IEC61000-4-3)

Test level 10V/m, performance criterion A

Electrical fast transient burst immunity (see IEC61000-4-4)

 

signal line port: ± 2KV, 
auxiliary power port: ± 2KV, performance criterion A

Conducted immunity of RF electromagnetic field induction (see IEC61000-4-6)

Test level 10V, performance criterion A